Glossary entry (derived from question below)
English term or phrase:
anti-surge
Bulgarian translation:
(за ел. предпазител) със забавено действие; бавнодействащ
Added to glossary by
invguy
Apr 21, 2011 13:20
13 yrs ago
4 viewers *
English term
anti-surge
English to Bulgarian
Tech/Engineering
Electronics / Elect Eng
Control Module
Здравейте,
Търся помощ за точния превод на израза на български.
Терминът се среща при описание на изходите на модула.
(Recommended Maximum Fuse 15A anti-surge)
Supplies the module (2A anti-surge requirement) and all output relays
Благодаря предварително!
Търся помощ за точния превод на израза на български.
Терминът се среща при описание на изходите на модула.
(Recommended Maximum Fuse 15A anti-surge)
Supplies the module (2A anti-surge requirement) and all output relays
Благодаря предварително!
Proposed translations
(Bulgarian)
4 | (в случая) със забавено действие; бавнодействащ | invguy |
4 | антипомпажен | Irolinda |
4 | устойчивост на пренапрежение | Yavor Popov |
3 | Защита от пренапрежение | Denis Shepelev |
Change log
Apr 24, 2011 23:05: invguy Created KOG entry
Proposed translations
20 hrs
Selected
(в случая) със забавено действие; бавнодействащ
Anti-surge protection действително значи защита от пренапрежение. Тук обаче (и в двата случая) става дума за предпазители, т.е. за максималнотокова защита. При предпазителите anti-surge = slow-blow = time delay (fuse).
The time delay fuse (also known as anti-surge, or slow-blow) are designed to allow a current which is above the rated value of the fuse to flow for a short period of time without the fuse blowing.
http://en.wikipedia.org/wiki/Fuse_(electrical)
Fuse Type
There are three basic types of fuses:
(1) Slow Blow/Time Lag/ Time Delay fuses
(2) Fast acting fuses
(3) Very fast acting fuses
. . . . .
Slow-blow fuse allows temporary and harmless inrush currents to pass without opening, but is so designed to open on sustained overloads and short circuits. Slow-blow fuses are ideal for circuits with a transient surge or power-on inrush. These circuits include: motors, transformers, incandescent lamps and capacitate loads. This inrush may be many times the circuit's full load amperes. Slow-blow fuses allow close rating of the fuse without nuisance opening. Typically, Slow Blow fuses are rated between 125% to 150% of the circuit's full load amperes.
http://www.circuitprotection.ca/fuseology.html
Slow Blow Fuses help provide overcurrent protection on systems
that experience large and frequent current surges as part of their
normal operation, and feature clear time characteristics of:
• 4 hours minimum at 100% of rated current;
• 120 seconds maximum and 1 second minimum at 200% of
rated current;
• 3 seconds maximum and 0.1 second minimum at 300% rated
current; and
• ranges from 0.0005 seconds minimum to 0.05 second
maximum at 800% of rated current.
http://docs.google.com/viewer?a=v&q=cache:f-KL88RmfwIJ:www.c...
На български се използва и "бавностопяем" (НЕ "бавнотопим"!), но то е по-разговорно.
The time delay fuse (also known as anti-surge, or slow-blow) are designed to allow a current which is above the rated value of the fuse to flow for a short period of time without the fuse blowing.
http://en.wikipedia.org/wiki/Fuse_(electrical)
Fuse Type
There are three basic types of fuses:
(1) Slow Blow/Time Lag/ Time Delay fuses
(2) Fast acting fuses
(3) Very fast acting fuses
. . . . .
Slow-blow fuse allows temporary and harmless inrush currents to pass without opening, but is so designed to open on sustained overloads and short circuits. Slow-blow fuses are ideal for circuits with a transient surge or power-on inrush. These circuits include: motors, transformers, incandescent lamps and capacitate loads. This inrush may be many times the circuit's full load amperes. Slow-blow fuses allow close rating of the fuse without nuisance opening. Typically, Slow Blow fuses are rated between 125% to 150% of the circuit's full load amperes.
http://www.circuitprotection.ca/fuseology.html
Slow Blow Fuses help provide overcurrent protection on systems
that experience large and frequent current surges as part of their
normal operation, and feature clear time characteristics of:
• 4 hours minimum at 100% of rated current;
• 120 seconds maximum and 1 second minimum at 200% of
rated current;
• 3 seconds maximum and 0.1 second minimum at 300% rated
current; and
• ranges from 0.0005 seconds minimum to 0.05 second
maximum at 800% of rated current.
http://docs.google.com/viewer?a=v&q=cache:f-KL88RmfwIJ:www.c...
На български се използва и "бавностопяем" (НЕ "бавнотопим"!), но то е по-разговорно.
4 KudoZ points awarded for this answer.
Comment: "Благодаря!"
13 mins
антипомпажен
Термина се среща в съчетания като антипомпажен кран, антипомпажна система за регулиране на компресора, антипомпажен клапан, т.н.
Example sentence:
"Настройка на 2 (два) броя антипомпажни регулатори, от които 1 бр. на КС „Кардам-2” и 1 бр. на КС „Лозенец”
Peer comment(s):
neutral |
Ivan Klyunchev
: Това не е ли за газопреносни инсталации? Имал съм го в такъв контекст. Тук е ел./елн.
9 hrs
|
25 mins
устойчивост на пренапрежение
Peer comment(s):
neutral |
Ivan Klyunchev
: Според мен тук anti-surge е прилагателно. Ми да, в линка е устойчив на пренапрежения.
9 hrs
|
27 mins
Защита от пренапрежение
Предпазител 15А със защита от пренапрежение.
Нещо такова.
Нещо такова.
Example sentence:
ПРЕДПАЗИТЕЛ ОТ ПРЕНАПРЕЖЕНИЕ 110V-240V 16A SURGE PROTECTOR EL-SPP01
Peer comment(s):
neutral |
Ivan Klyunchev
: Според мен тук anti-surge е прилагателно.
9 hrs
|
Естествено, че е прилагателно.
|
Something went wrong...